DISPLAY ・Color LCD 3.5 inches dot matrix.
ATT ・Anti-Trip Technology (with 2 & 3 wire) for no trip LOOP L-PE testing on all RCDs.
・With 2 wire only, very useful in case of no Neutral (i.e. 3-phase motor lines).
LOOP ・High test current range of 2Ω with 0.001Ω resolution.
・Zs Limit compares the values required by Electrical Installations Standard with
measured results.
RCD ・Type AC, A, F, B(General & Selective), EV and Variable RCDs.
・Single and Autotest, Ramp test and Contact voltage.
EARTH ・Earth resistance test 2 and 3 wires with all accessories included.
INSULATION ・Resistance test 100, 250, 500 & 1000V with auto discharge voltage.
CONTINUITY ・Continuity test at 200mA or 15mA with selectable buzzer for fast judgment.
PHASE ROTATION ・On 3-phase lines with a clear indication of the sequence on the display.
VOLTS ・TRMS Voltage measurements 2-600V, Mains Frequency.
HELP ・Display shows how to connect the instrument according to the function selected.
SPD ・Surge Protection Device test, for SPD that uses varistor.
PAT ・Portable Appliance Tester function, for Insulation and Protective inductor resistance test
Bluetooth ・Communication by "KEW CONNECT"
SAFETY ・IEC 61010-1 CAT IV 300 V, CAT III 600 V. IEC 61557-1,2,3,4,5,6,7,10.
Insulation resistance | SPD(Varistor) | ||||
---|---|---|---|---|---|
Test voltage |
100V | 250V | 500V | 1000V | Max.1000V |
Measuring ranges |
2.000/20.00/200.0MΩ (Auto-ranging) |
20.00/200.0/1000MΩ (Auto-ranging) |
20.00/200.0/2000MΩ (Auto-ranging) |
0-1000V (goes up by 1V) |
|
Accuracy | ±2%rdg±6dgt (2.000/20.00MΩ) ±5%rdg±6dgt (200.0MΩ) |
±2%rdg±6dgt (20.00/200.0MΩ) ±5%rdg±6dgt (1000MΩ) |
±2%rdg±6dgt (20.00/200.0MΩ) ±5%rdg±6dgt (2000MΩ) |
±5%rdg±5dgt | |
Rated current |
1.0-1.2mA @0.1MΩ |
1.0-1.2mA @0.25MΩ |
1.0-1.2mA @0.5MΩ |
1.0-1.2mA @1MΩ |
‐ |
Short circuit current | 1.5mA max | ‐ |
Loop impedance | |||||
---|---|---|---|---|---|
Function | LOOP ATT | LOOP HIGH | |||
L-PE/L-N (3wire) |
L-PE(2wire) | L-PE (0.01ΩRes) |
L-PE (0.001ΩRes) High test current(25A) |
L-N/L-L | |
Rated voltage |
100-260V (50/60Hz) |
48-260V (50/60Hz) |
48-260V (50/60Hz) |
100-260V (50/60Hz) |
48-500V (50/60Hz) |
Impedance range |
20.00/200.0/2000Ω (Auto-ranging) |
20.00/200.0/ 2000Ω (Auto-ranging) |
2.000Ω | 20.00Ω | |
Accuracy | ±3%rdg±6dgt | ±3%rdg±10dgt | ±3%rdg±4dgt | ±3%rdg±25mΩ | ±3%rdg±4dgt |
Nominal test current at 0Ω external loop: Magnitude/ Duration at 230V |
L-N:6A/60ms N-PE:10mA |
L-PE:15mA | 20Ω: 6A/20ms 200Ω: 0.5A/20ms 2000Ω: 15mA/500ms |
25A/20ms |
6A/20ms |
PSC/PFC | |||||
---|---|---|---|---|---|
Range |
2000A/20kA |
2000A/20kA (PFC) |
2000A/20kA (PFC) |
2000A/50kA (PFC) |
2000A/20kA (PSC) |
Accuracy | PSC/PFC accuracy is derived from measured loop impedance specification and measured voltage specification |
RCD | ||||||||
---|---|---|---|---|---|---|---|---|
Rated voltage | 100-260V(50/60Hz) | |||||||
Function | x1/2, x1,x5,Ramp,Auto,Uc | |||||||
6/10/30/100/300/500/1000mA/variable | ||||||||
RCD type | AC(G/S) | A(G/S) | F(G/S) | B(G/S) | EV | |||
Trip current setting |
x1/2, x1,Uc |
10/30/100/300/ 500/1000mA(G) 10/30/100/ 300/500(S) |
10/30/100/ 300/500mA |
10/30/100/ 300/500mA |
10/30/100/ 300mA |
6mA(x1 only) | ||
x5 | 10/30/100mA | 10/30/100mA | 10/30/100mA | 10/30mA | - | |||
Ramp | 10/30/100/ 300/500mA |
10/30/100/ 300/500mA |
10/30/100/ 300/500mA |
10/30/100/ 300mA |
6mA | |||
Accuracy | ||||||||
Trip current |
x1/2 | -8% - -2% | -10% - 0% | -10% - 0% | -10% - 0% | - | ||
x1 | +2% - +8% | 0% - +10% | 0% - +10% | 0% - +10% | 0% - +10% | |||
x5 | +2% - +8% | 0% - +10% | 0% - +10% | 0% - +10% | - | |||
Ramp | -4% - +4% | -10% - +10% | -10% - +10% | -10% - +10% | -10% - +10% | |||
Trip time |
x1/2 | 2000ms(G/S):±1%rdg±2ms | - | |||||
x1 | 550ms(G):±1%rdg±2ms,1000ms(S):±1%rdg±2ms | 10.5s:±1%±2㎳ | ||||||
x5 | 410ms(G/S):±1%rdg±2ms | - |
Continuity | ||||
---|---|---|---|---|
Range | 20.00/200.0/2000Ω (Auto-ranging) | |||
Open circuit voltage(DC) | 7-14V | |||
Measuring current | 200mA | >200mA or more(2Ω or less) | ||
15mA | 15mA±3mA(short-circuit) | |||
Accuracy | ±2%rdg±8dgt |
Volts | ||||
---|---|---|---|---|
Range | 300.0/600V(Auto-ranging) | |||
Measuring ranges | Volts | 2-600V | ||
Frequency | 45-65Hz | |||
Accuracy | Volts | ±2%rdg±4dgt | ||
Frequency | ±0.5%rdg±2dgt |
Phase Rotation | ||||
---|---|---|---|---|
Rated voltage |
Rated voltage | 48-600V(50/60Hz) | |||
---|---|---|---|---|
Remarks | Remarks Correct phase sequence: are displayed “1.2.3” and mark Reversed-phase sequence: are displayed “3.2.1” and mark |
Earth | ||||
---|---|---|---|---|
Range | 20.00/200.0/2000Ω(Auto-ranging) | |||
Accuracy | ±2%rdg±0.08Ω(20.00Ω) ±2%rdg±3dgt(200.0/2000Ω) |
Applicable standards | IEC 61010-1 CAT IV 300V, CAT III 600 V Pollution degree 2 IEC 61010-2-034 IEC 61557-1,2,3,4,5,6,7,10 IEC 60529(IP40) IEC 61326(EMC) |
---|---|
Power source | LR6 (AA) (1.5V) ×8 |
Communication interface | USB, Bluetooth®5.0, Android™5.0 or more, iOS 10.0 or more ※1 |
Dimensions / Weight | 136(L) × 235(W) × 114(D) mm / Approx. 1300g (including batteries) |
Included Accessories | Main test lead※2 7281(Test leads with remote control switch) 7246(Distribution board test lead) 7228A(Earth resistance test leads) 8041(Auxiliary earth spikes[2 spikes/1 sets]) 9084(Soft Case) 9142(Carrying case) 9151(Shoulder strap) 9199(Shoulder pad) LR6(AA) × 8, Instruction manual, Calibration certificate |
Optional Accessories | 8212-USB(USB adaptor with "KEW Report(Software)'') 8259(Adapter for measurement terminal) 7272(Precision measurement Cord set) 8017A(Extension prod long) |
※1 Bluetooth is a trademark or registered trademark of Bluetooth SIG. Inc.
Android is a trademark or registered trademark of Google Inc.
iOS is a trademark or registered trademark of Cisco Technology, Inc. in the United States and other countries.
※2 7187A: British plug, 7218A:(EU)European SHUKO plug, 7221A:(SA)South African plug, 7222A:(AU)Australian plug
For no trip LOOP L-PE testing on all RCDs.
With 3 wire (L, N, PE), to get the best accuracy readings.
With 2 wire only, very useful in case of no Neutral (i.e. 3-phase motor lines).
High test current range of 2Ω with 0.001Ω resolution.
Zs Limit compares the values required by Electrical Installations Standard with measured results.
The verification of safety requirements on an electrical installation is simplified by using Zs/Ra Limit function. This function will automatically check if the measured loop impedance for TN (or earth loop for TT) is low enough to trip (disconnect) the MCB / Fuse / RCD giving the result of PASS or FAIL on the display.
SPD (Surge Protection Device) which contains varistor can be tested measuring the tripping voltage without damage it.
PAT test (PAT = Portable Appliance Tester) It is possible to check the insulation resistance and earth bond continuity of portable appliances for class I and II.
Use the application KEW Smart* to improve work efficiency.
KEW 6516BT can transfer the test data toa Tablet or Smartphone via Bluetooth.
Such test data can be saved, shared, and sent by email.
Please search "KEW Smart"
Communication charges may be incurred separately to download applications.
Application for Android Free Android software "KEW Power" is available on "Google Play Store" Supporting Android ver.5.0
Application for iOS Free iOS software "KEW Power" is available on "APP Store" Supporting iOS 10.0
Use the PC application Kew Report to improve work efficiency.
KEW 6516BT can download the test data by connecting the USB adaptor (Model 8212-USB for option) and then print complete Test Reports by a PC.
Accessories/Optional Accessories /Related Products
MODEL 7187A,7218A,7221A,7222A | |
MODEL 7281 | |
|
MODEL 7246/7247 |
MODEL 7228A | |
MODEL 8041 | |
MODEL 9084 | |
MODEL 9142 |
MODEL 9151 |
|
MODEL 9199 | |
MODEL 8212-USB | |
MODEL 8259 | |
MODEL 7272 | |
MODEL 8017A |